電動機保護器種類很多,推薦一種上海碩吉JD-5S電動機綜合保護器及(ji)接線方式,220/380可選。
指 標 |
規 格 |
|
電動機保護器型號 |
JD-5S |
JD-5C |
整定(ding)電流(liu)范圍 |
5~80A |
0.5~10A |
過載(zai)動作時間 |
1~99秒 |
|
電源電壓 |
220V或380V(以產品(pin)標簽為準),其他電壓可定(ding)制 |
電動機缺相保護器工作原理和接線圖
保護器在斷電狀態下(xia),NC與CO是通的。通電后,電動機工作正常時保持接通,當檢測到電動機出現故障時,繼電器斷開,切斷電動機電源。
缺相(xiang)(xiang)(xiang)就是三(san)相(xiang)(xiang)(xiang)電(dian)(dian)(dian)(dian)源(yuan)(yuan)供(gong)電(dian)(dian)(dian)(dian),實際到(dao)的不是三(san)相(xiang)(xiang)(xiang),而是兩(liang)相(xiang)(xiang)(xiang)或只有一(yi)相(xiang)(xiang)(xiang)電(dian)(dian)(dian)(dian)。三(san)相(xiang)(xiang)(xiang)電(dian)(dian)(dian)(dian)機(ji)電(dian)(dian)(dian)(dian)源(yuan)(yuan)缺相(xiang)(xiang)(xiang)后(hou)電(dian)(dian)(dian)(dian)機(ji)無法(fa)正常工作(zuo),長時(shi)間缺一(yi)相(xiang)(xiang)(xiang)電(dian)(dian)(dian)(dian)會燒壞電(dian)(dian)(dian)(dian)機(ji)線圈繞組(zu),使(shi)用三(san)相(xiang)(xiang)(xiang)380V電(dian)(dian)(dian)(dian)源(yuan)(yuan)變220V控制電(dian)(dian)(dian)(dian)源(yuan)(yuan),會因為缺相(xiang)(xiang)(xiang)沒有220V電(dian)(dian)(dian)(dian)壓(ya)(ya)。可(ke)以使(shi)用萬用表測量三(san)相(xiang)(xiang)(xiang)電(dian)(dian)(dian)(dian)源(yuan)(yuan)相(xiang)(xiang)(xiang)間電(dian)(dian)(dian)(dian)壓(ya)(ya),如果不都(dou)是380V左右,說(shuo)明電(dian)(dian)(dian)(dian)源(yuan)(yuan)缺相(xiang)(xiang)(xiang)。
電流檢測
電(dian)(dian)動(dong)機保護器(qi)(qi)通(tong)過內置(zhi)的(de)(de)電(dian)(dian)流互(hu)(hu)感器(qi)(qi)來檢(jian)測三相負載電(dian)(dian)流,所以被保護電(dian)(dian)動(dong)機的(de)(de)三根相線(xian)必(bi)須分別穿過電(dian)(dian)流互(hu)(hu)感器(qi)(qi)的(de)(de)三個小孔
??????過載保護
當負載電(dian)(dian)流超(chao)過整定電(dian)(dian)流,并且(qie)持續時(shi)間達到設定的(de)過載動作時(shi)間時(shi),繼(ji)電(dian)(dian)器斷(duan)開,切(qie)斷(duan)電(dian)(dian)動機電(dian)(dian)源。
智能(neng)啟動識別(bie)
為防止電機啟動時產生誤動作(zuo),本(ben)產品具(ju)有智能(neng)啟動識(shi)別功能(neng),當(dang)識(shi)別到電動機處于啟動狀態時,過載動作(zuo)時間加倍。
缺相(xiang)保(bao)護
當(dang)電(dian)(dian)動(dong)機(ji)(ji)發生缺(que)相故障(zhang)時(shi),繼電(dian)(dian)器斷(duan)開(kai),切斷(duan)電(dian)(dian)動(dong)機(ji)(ji)電(dian)(dian)源。為防止空載和(he)小電(dian)(dian)流時(shi)誤動(dong)作,電(dian)(dian)流小于2A時關閉缺相檢測。
相(xiang)關閱讀:
●電機綜合保護器接線圖(電機保護裝置和星三角啟動裝置線路圖)